Build Load Forecast Scenarios From Drivers, Not Percentage Bands
Why scaling a reference load forecast up and down fails scenario requirements, and how to build high and low cases from electrification and weather drivers.
Topics: Utilities & Energy, Data Engineering
On this page
Most distributor load forecasts were built to produce one weather-normal reference number per year. When a regulator asks for high and low cases, the quick fix is to scale that reference up and down by a fixed percentage. It looks like a scenario set, but it isn’t one. It falls apart the first time someone asks why the high case is high.
What the requirement actually asks for
In Ontario, the OEB’s Chapter 2 filing requirements for electricity distributors (2026 edition for 2027 rate applications, published December 16, 2025) set this out in section 2.3.1.3. Load forecasts must include reference, high and low demand scenarios that account for electrification. They must also reflect employment, population and housing projections and future average, minimum and maximum temperatures. As of October 2026, distributors are expected to make best efforts from June 30, 2026. The requirement is mandatory for applications filed after April 1, 2027, which means rates effective January 1, 2028 or later. (OEB filing requirements)
Three things follow from that wording:
- The requirement defines scenarios by their inputs, not by their spread.
- Temperature is a future assumption, not only a historical normal.
- The OEB says “a distributor may use modelling done by others.” You can buy scenarios, but you still have to explain them.
How your regulatory team reads and files against the requirement is their call. What follows is the engineering side.
Why percentage bands fail
- No traceability. You can’t answer “what heat pump adoption does the high case assume?” because the high case doesn’t assume anything.
- Wrong shape. Electrification doesn’t scale load uniformly. It moves winter peak more than annual energy, and EV charging reshapes the evening hours. A single multiplier moves energy and peak together.
- Disagreement with the capital plan. If system planning sizes stations on specific adoption assumptions and the rate forecast uses a band, the two documents tell different stories.
- Nothing to update. When a new housing projection arrives, there’s no input to change. You either redo the band by judgment or leave it stale.
Electrification changes the weather response
This is the mechanism most forecasts get wrong.
A typical distributor model regresses load on calendar effects, economic drivers and heating and cooling degree days. The heating coefficient was estimated on history, when most space heating ran on gas. As heat pumps displace furnaces, the system’s sensitivity to cold rises. That rise is nonlinear: at very low temperatures, heat pump efficiency falls and backup resistance heat switches on.
If you add electrification as a separate additive trajectory on top of a weather-normalized forecast, you lock in the old temperature sensitivity. You’ll understate peak in exactly the scenario that matters, a cold winter on a heavily electrified system.
Instead, model electrified end uses with their own temperature response:
- Heat pumps: units adopted × per-unit load as a function of hourly temperature, including the backup-heat region.
- EVs: vehicles adopted × charging profile, with a smaller cold-weather adjustment.
- Base load: your existing model, re-estimated so it isn’t double-counting heating that has since moved to the electrified layer.
Drive all three layers from the same hourly temperature series so the scenarios stay consistent.
Averages hide the peak
The requirement names minimum and maximum temperatures for a reason. Energy follows the average, but extremes set the peak. A warming trend in average temperature can lower winter energy while a single cold snap still sets a new peak on an electrified system. Run each scenario across a range of weather years. Report energy against average conditions and peak against extremes.
If you want public data to test the hourly temperature-response layer before using your own meter data, the EIA-930 dataset has it. As of October 2026, it publishes each U.S. balancing authority’s hourly demand alongside that authority’s own day-ahead forecast, starting July 1, 2015. (EIA-930)
Make the assumptions table the deliverable
The forecast output is a product of the assumptions, so treat the assumptions as the primary artifact:
| Driver | Low | Reference | High | Source | Vintage |
|---|---|---|---|---|---|
| Heat pump adoption | path | path | path | named study | date |
| EV adoption | path | path | path | named study | date |
| Housing starts | path | path | path | municipal or provincial projection | date |
| Employment, population | path | path | path | named projection | date |
| Temperature (avg, min, max) | path | path | path | climate dataset | date |
Version this table the same way you version data. Every forecast run should record which table version produced it, so a number in an application traces back to its inputs. The Immutable Data Lake and The Lineage Imperative cover the plumbing for this.
If you use modelling done by others, ask for this table, not just the output curves. Without it, you can’t defend the scenarios or update them.
Checks before anything goes into an application
- Ordering: low ≤ reference ≤ high for both energy and peak in every year. Document any crossover rather than smoothing it away.
- Decomposition: attribute the gap between each scenario and the reference to individual drivers. If one driver explains nearly everything, the others are decoration.
- Coherence: each combination of drivers should be plausible. A high case that pairs fast heat pump adoption with low housing growth needs a written reason.
- Backtest first: validate the re-estimated base model on held-out years before you layer electrification on top. Otherwise you can’t tell base-model error from adoption error.
- Peak vs. energy: confirm the high case raises peak more than energy in winter-peaking territory. If both rise by the same proportion, you’ve rebuilt a percentage band.
If you’re rebuilding a distributor forecast for these requirements, you can talk to us.